Ventilation Smoke Detector System LRS 01
Ventilation smoke detector system LRS 01 for mounting on ventilation ducts with round or rectangular cross-section for early smoke detection.
The special features are:
- Visible operation and contamination display from the outside
- Alarm storage
- For air speeds up to 20 m/s
- Flow-optimized 2-pipe airflow system
- Easy installation without additional console
- Tool-free testing, maintenance, cleaning
- Simple removal of the inlet pipe during maintenance
- Potential-free contact opens on alarm and fault
Technical Data Housing
Technical Data of the Integrated Smoke Detector ORS 210
Ventilation smoke detector system LRS 01 for mounting on ventilation ducts with round or rectangular cross-section for early smoke detection.
The special features are:
- Visible operation and contamination display from the outside
- Alarm storage
- For air speeds up to 20 m/s
- Flow-optimized 2-pipe airflow system
- Easy installation without additional console
- Tool-free testing, maintenance, cleaning
- Simple removal of the inlet pipe during maintenance
- Potential-free contact opens on alarm and fault
Technical Data Housing
Inlet pipe: | Installation depth 350 mm |
per inlet hole: | 100 mm channel depth |
Cable entry: | 4 x 6 to 10 mm (M16) |
Protection class outside: | IP 54 |
Color: | blue, translucent cover |
Maintenance: | annually |
Technical Data of the Integrated Smoke Detector ORS 210
Smoke detection: | according to EN 54, Part 7 |
Operating voltage: | 16 to 28 V DC |
Current consumption at 28 V DC: | |
Standby: | 22 mA |
Alarm: | 11 mA |
Fault: | 16 mA |
Relay contact: | Normally open |
Switching voltage: | 30 V DC |
Switching current: | 1 A |
Protection class: | IP 40 |
Operating ambient temperature: | -20°C to +60°C |
Weight: | 120 g |
Periodic monitoring: | annual maintenance |
Technical data | |
Protection class | IP 54 |