• System LRS 03
Ventilation Smoke Detector System LRS 03

The ventilation smoke detector system LRS 03 is designed for installation on ventilation ducts with round or rectangular cross-sections for early smoke detection.
The special features are:
- Autonomous system decoupled from BSK
- Long operational readiness due to processor-controlled pollution compensation
- Visible operational and pollution display from the outside
- Easy installation without additional console
- Tool-free testing, maintenance, cleaning
- Simple cleaning of the smoke inlet pipe
- Alarm release button mounted on the housing for quick testing
- Maintenance only once a year

Technical Data Housing
Inlet pipe:Maximum installation depth 345 mm
Cable entry:4 x 6 to 10 mm (M16)
Protection class external:IP 54
Color:blue, clear cover

Technical Data of Integrated Smoke Detector ORS 144 K
Smoke detection:according to EN 54, Part 7
Operating voltage:21.6 to 28 V DC
21.6 to 26 V AC
Current consumption at 28 V AC/DC:
  Standby:26 mA
  Alarm:15 mA
  Fault:20 mA
Relay contact:Normally open
  Switching voltage:30 V DC
  Switching current:1 A
  Switching power:30 W
Operating ambient temperature:-20°C to +60°C
Technical data
Protection class IP 54