• Smoke Switch ORS 142
Smoke Detector ORS 142

Optical smoke detector for smoldering fires and open fires with smoke development.
Its special features are: - Alarm threshold tracking
- Optical contamination/state indication
- Measuring chamber monitoring
- Communication connection for RSBus
- Potential-free relay
- Thermoelement for triggering at an ambient temperature > 70°C.

Smoke detection:according to EN 54, part 7
Temperature:70°C
Operating voltage:18 to 28 V DC
Current consumption at 28 V DC: 
  Idle:22 mA
  Alarm:11 mA
  Fault:16 mA
Relay contact:Normally open
  Switching voltage:30 V DC
  Switching current:1 A
  Switching power:30 W
Protection class:IP 42
Operating ambient temperature:-20°C to +60°C
Color:white, similar to RAL 9010

Technical data
Color White

Smoke Switch ORS 142

  • Brand: Hekatron 
    [Info]

    Hekatron Technik GmbH
    Brühlmatten 3a - 9
    79295 Sulzburg
    T: +49 7634 500-0
    hekatron.de
    manufacturing@hekatron.de

  • Product Code: 5000552-0501
  • Availability: In Stock