Ventilation Smoke Detector System LRS 01
Ventilation smoke detector system LRS 01 for mounting on ventilation ducts with circular or rectangular cross-section for early smoke detection.
The special features are:
- Visible operational and pollution indicators from the outside
- Alarm storage
- For air speeds up to 20 m/s
- Optimized 2-pipe airflow system
- Easy installation without additional console
- Tool-free testing, maintenance, cleaning
- Easy removal of the intake pipe during maintenance
- Potential-free contact opens on alarm and fault
Technical Data Housing
Technical Data of the Integrated Smoke Detector ORS 210
Ventilation smoke detector system LRS 01 for mounting on ventilation ducts with circular or rectangular cross-section for early smoke detection.
The special features are:
- Visible operational and pollution indicators from the outside
- Alarm storage
- For air speeds up to 20 m/s
- Optimized 2-pipe airflow system
- Easy installation without additional console
- Tool-free testing, maintenance, cleaning
- Easy removal of the intake pipe during maintenance
- Potential-free contact opens on alarm and fault
Technical Data Housing
Intake pipe: | Installation depth 350 mm |
per intake hole: | 100 mm duct depth |
Cable entry: | 4 x 6 to 10 mm (M16) |
Protection class outside: | IP 54 |
Color: | blue, cover clear |
Maintenance: | annual |
Technical Data of the Integrated Smoke Detector ORS 210
Smoke detection: | according to EN 54, part 7 |
Operating voltage: | 16 to 28 V DC |
Current consumption at 28 V DC: | |
Standby: | 22 mA |
Alarm: | 11 mA |
Fault: | 16 mA |
Relay contact: | Normally open |
Switching voltage: | 30 V DC |
Switching current: | 1 A |
Protection class: | IP 40 |
Operating ambient temperature: | -20°C to +60°C |
Weight: | 120 g |
Periodic monitoring: | annual maintenance |
Technical data | |
Protection class | IP 54 |