• System LRS 02
Ventilation Smoke Detector System LRS 02

The ventilation smoke detector system LRS 02 is designed for installation on ventilation ducts with a round or rectangular cross-section for early smoke detection.
The special features are:
- Visible operational and contamination indicator from the outside
- Alarm storage
- For air speeds of up to 20 m/s
- Streamlined 2-pipe airflow system
- Easy installation without additional console
- Tool-free testing, maintenance, cleaning
- Simple removal of the inlet pipe during maintenance
- Potential-free contact opens in case of alarm and fault

Additional special features:
- Connection to 24 V AC/DC (alternating/direct current)
- Alarm reset button
- Pre-wired comfort connection terminals for external cables for easier and faster installation

Technical Data Housing
Inlet pipe:Installation depth 350 mm
per inlet opening:100 mm duct depth
Cable entry:4 x 6 to 10 mm (M16)
Protection class exterior:IP 54
Color:blue, cover clear
Maintenance:annually

Technical Data of the Integrated Smoke Detector ORS 210
Smoke detection:according to EN 54, Part 7
Operating voltage:16 to 28 V DC
Current consumption at 28 V DC:
  Idle:22 mA
  Alarm:11 mA
  Fault:16 mA
Relay contact:Normally open
  Switching voltage:30 V DC
  Switching current:1 A
Protection class:IP 40
Operating ambient temperature:-20°C to +60°C
Weight:120 g
Periodic monitoring:annual maintenance
Technical data
Protection class IP 54

System LRS 02

  • Brand: Hekatron 
    [Info]

    Hekatron Technik GmbH
    Brühlmatten 3a - 9
    79295 Sulzburg
    T: +49 7634 500-0
    hekatron.de
    manufacturing@hekatron.de

  • Product Code: 5000619-0401
  • Availability: In Stock